Product Content Description:

Flatpack2 48V 2000W Super HE  Eltek Rectifier Module 241119.106
 
APPLICATIONS
 
TELECOM - WIRELESS
Radio base station / Cell sites
LTE / 4G / WiMAX
Mobile switching center (MCS)
Microwave
Broadband
TELECOM - FIXED
Central office
Telephony servers / switches
Fiber optics
Microwave
Broadband
Broadcast
Data center
 
Key Features
 
SUPER HIGH EFFICIENCY – 97.8%
HIGH POWER DENSITY – 33 W/IN3
COMPATIBLE WITH EXISTING SYSTEMS
GLOBAL COMPLIANCE
PATENTED TECHNOLOGY
HOT PLUGGABLE
 
Super High Efficiency (SHE) rectifiers for Telecom applications
 
The Flatpack2 48V Super HE rectifiers are contributing to setting the new industry standard for efficiency in the DC power market.
With an efficiency of 97.8% the Super HE is a premium rectifier particularly suitable for markets and applications where the energy is costly. In grid connected applications the payback time is down to 2 years compared to standard HE rectifiers, and in hybrid applications even faster.
The Flatpack2 Super HE is fully compatible with Flatpack2 and Flatpack2 HE systems and can replace any Flatpack2 48V rectifier module.
 
Specifications
 
Model 48/3000 SHE
Part number 241119.106
INPUT DATA  
Voltage (nominal range) 206 - 264 VAC
Voltage (operating range) 85 - 264 VAC
Frequency 45 - 66 Hz
Maximum current 16 ARMS
Protection Fuse in Live, varistor for transient protection, shutdown when VIN  is out of range
OUTPUT DATA  
Voltage (default) 53.5 VDC
Voltage (adjustable range) 43.21)  - 57.6 VDC
Max power, nominal input 3000 W
Max power, de-rated @VIN  = 85 VAC 1000 W
Max current, @VOUT  = 48 VDC 62.5 A
Current sharing ±5.0% of max current
Static voltage regulation (10-100% load) ±0.5%
Dynamic voltage regulation ±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms
Hold up time (3000W load) >10ms; output voltage > 42 VDC
Ripple <150 mVPP , 30 MHz bandwidth
 
Protection
Overvoltage shutdown, short circuit proof, high temperature, hot plug-in inrush current limiting, fuse
OTHER SPECIFICATIONS  
Peak Efficiency 97.8 %
 
Isolation
3.0 kVAC  – input to output
1.5 kVAC  – input to protective earth
0.5 kVDC  – output to protective earth
 
Alarms (Red LED)
Low mains shutdown, High and low temperature shutdown, Rectifier Failure, Overvoltage shutdown on output, Fan failure, Low voltage alarm, CAN bus failure
 
Warnings (Yellow LED)
Rectifier in power derate mode, Remote current limit activated, Input voltage out of range, flashing at overvoltage
Normal (Green LED) Input and output ok
MTBF (Telcordia SR-332 Iss.3 method II Case L1) 1 900 000 hours
Operating temperature (5 - 95% RH non-cond.) -40 - 75°C [-40 - 167°F ]
Max output power de-rates above temp / to 45°C [+113°F] / 1800 W 2)
Storage temperature -40 to +85°C (-40 to +185°F),  humidity 0 - 99% RH non-condensing
Dimensions[WxHxD] / Weight 109 x 41.0 x 327mm [4.25 x 1.61 x 13”] /  2.050 kg [4.5lbs]
DESIGN STANDARDS  
Electrical safety EN 60950-1:2006+A11:2009+A1:2010+A12:2011+A2:2013, UL 60950-1:2014
EMC EN 61000-6-1:2019, -6-2:2019, - 6-3:2007 + A1:2011, - 6-4:2019
ETSI EN 300 386 V.2.1.1, FCC CFR 47 Part 15:2013
 
Environment
ETSI EN 300 019: 2-1 (Class 1.2) & 2-2 (Class 2.3) EU 2015/863 (RoHS) & 2012/19/EU (WEEE)
Normal operating conditions as per IEC 62040-5-3:2016 clause 4.2. Other operating conditions as per IEC 62040-5-3:2016 clause 4.3, must be advised
 
1) Stand-by / test operation (V OUT < 48VDC) limited for VIN > 230 VAC
2) When input mains voltage is below 210 VRMS temperature derating will start at 40 °C and 1500 W will be available at 75 °C

Send your inquiry to this supplier