Wuhan Unique Mechanical And Electrical Equipment Co., Ltd.
Home > Products > Communication Equipments/n.e.s. > Flatpack2 220v 2000W HE Rectifiers Eltek Rectifier Module 241115.815

Flatpack2 220v 2000W HE Rectifiers Eltek Rectifier Module 241115.815

—-, Eltek, 241115.815, power supply
Product Category: Communication Equipments/n.e.s.
Sales Method: Export, Manufacture, OEM/ODM
Payment Term: T/T, L/C
Trade Term (Incoterms): FOB, CIF
Min. Order Unit Price
1 Piece USD 1 / Piece
Contact Info

Mr.John Zou

Address: China (mainland) Hubei Wuhan,Room B813, No. 61, Yejin Avenue, Qingshan District, Wuhan City, Hubei Province, China.

Product Detail

Product Attribute:

  • China (mainland) More >
  • -
  • UNIQUE
  • -
  • -
  • -40C ~70C (-40F ~ 158F)
  • 06/17/2020
  • 06/18/2020

Product Content Description:

Flatpack2 220v 2000W HE Rectifiers  Eltek Rectifier Module 241115.815
 
High efficiency and reliable rectifiers
The most  efficient  power conversion module  in the industry! Since the launch the Flatpack2 family has expanded into a wide selection of power ratings and voltages.
Power  systems  up  to  the  MW-range can  be realized using the 10A model  addressing  small and larger modular data centers’ power needs. 220VDC power systems provide an excellent alternative to traditional AC UPS providing significant efficiency and reliability improvements.
With 220V DC, standard components, cables and distribution can be used and most IT equipment designed for 208/ 230V AC can be connected directly to the 220V DC  bus.
 
Applications
 
Power Utilities
Switch Tripping
Control & Protection Systems
Emergency Lighting
Railway Infrastructure
Converter Stations
Power Stations
Marine And Off-Shore
Central Power System
Data Center
Central Power System
Dc/ Dc - Isolate Branches
 
Specifications
 
Part number 241115.815
Model 220 / 2000 HE WOR
INPUT DATA  
Voltage range 85 - 300 V AC/ DC
Voltage range (nominal) 185 - 275 V AC/ DC
Frequency 0 - 66 Hz
Maximum current 11.9 A RMS
Power Factor 0.99 (@ 50-100% load)
THD (@ 230 VAC) < 5 % (@ full load)
Protection Varistor  for transient  protection, fuse in both lines, shutdown above 300/ 305 V
OUTPUT DATA  
Default voltage 245.3 V DC
Voltage range 178.5 1)  - 297 VDC
# Pb cell supported (1.8 - 2.4 V DC/ cell) 108 - 122
# NiCad cell supported (1.05 - 1.65 V  DC/ cell) 170 - 180
Max power, nominal input 2000 W
Max power, 85V input 850 W
Max current, @220V DC 9.16 A
Hold-up time, default  voltage and 1500 W load 20 ms, VOUT > 178 V DC
Ripple and noise, 30 MHz bandwidth < 1000 mV PP
Current sharing ±5% of maximum current  from 10 to 100% load
Static  voltage regulation ±0.5% from 10% to 100% load and nominal input
Dynamic  voltage regulation ±5.0% for 10-90% or 90-10% load variation, regulation  time < 50ms
Protection Overvoltage shutdown, short circuit proof, high temperature, hot plug -in inrush current limiting, ORing diode
OTHER SPECIFICATIONS  
Efficiency > 95%
Isolation 3.0 kVAC – input to output, 1.5 kV AC – input to earth, 1.5 kV  DC – output to earth 3 kVAC – CAN to input, 3 kV AC – CAN to output, 500 V AC – CAN to earth
Alarms (Red LED) Low mains shutdown, High and low temperature shutdown, Rectifier Failure, Overvoltage shutdown on output, Fan failure, Low voltage alarm, CAN bus failure
Warnings (Yellow LED) Rectifier in power derate mode, Remote battery current limit activated, Input voltage out of range, flashing at overvoltage
Normal (Green LED) Input and output ok
MTBF (Telcordia SR-332 Issue I method III (a)) >391 000h (@T AMBIENT= 25°C)
Operating temperature (5 - 95% RH non-cond.) Output  power de-rates above temp / to -40 to +75°C [ -40 to +167°F]
+55°C / 1350W @ +75°C
Storage temperature -40 to +85°C (-40 to +185°F),  humidity 0 - 99% RH non-condensing
Dimensions[WxHxD] / Weight 109 x 41.5 x 327mm (WxHxD) [4.25 x 1.69 x 13”] /   1.950 kg [4.3lbs]
DESIGN STANDARDS  
Electrical safety UL 60950 -1, EN 60950 -1, CSA 22.2
EMC ETSI EN 300 386 V.1.3.2
EN 61000-6-1 / -2 /  -3 / -4 / -5
Mains Harmonics EN 61000 -3-2
Environment ETSI EN 300 019: 2-1 (Class 1.2), 2-2 (Class 2.3) & 2-3 (Class 3.2)
ETSI EN 300 132-2
2011/ 65/ EU (RoHS) & 2008/ 98/EC (WEEE)
Marine compliance
(EMC class B with AC filter)
DnV Rules for Classification of Ships, High Speed & Light Craft and DnV Offshore
Standards
 
1)  VOUT may increase at no and very light load (< 1 A) for V  OUT_SET < 245 V DC set and V IN > 250 V AC/ DC
2)  Specification valid for HW version  2 and newer. For older revision see DS:24111x.815.DS3 ver1.
3)  VRLA batteries boost  2.33V/ cell
4)  8A when V IN > 290V AC and Tambient  > 45°C and VOUT < 220V DC
 
 